Your browser is not up to date and is not able to run this publication.

35

Structure - Giving onto street and garden side: traditional construction - stone and plaster, wooden doors and windows.

- Atrium: curtain wall type. - Haussmann glass roof (8th floor) and Atrium (5th floor).

- Manual interior blinds to street and garden walls. - Electric blinds to atrium wall.

Windows - Wooden doors and windows.

Office suspended ceilings - Offices: mineral wool filled heavy thermolacquered metallic tiles, size 60 cm x 60 cm or 120 cm x 60 cm.

- Corridor: mineral wool filled EC3 metallic tiles - Sections of plasterboard.

Lighting - Suspended ceiling LED Lightning. - On/Off switch activated by presence detectors.

Loading capacity - Raised floor 250 kg/m² - 600 mm x 600 mm tiles with plenum space and buildings and 350 kg/m² directly on slab.

Floor to ceiling height - Between raised floor and suspended ceiling: Ground floor, 1st floor, 5th, 6th, 7th and 8th

floors, Haussmann side: 2.50 m. Heights on Chauchat, Le Peletier and Rossini

sides: 2.60 m. 2nd floor and 3rd floor, Haussmann side:

2.95 m. 4th floor, Haussmann side: 4.05 m.

HVAC - District heating produced by CPCU sub-station in basement.

- Hot water produced by individual immersion heaters.

- Disctrict chilled water produced by Climespace sub-station in basement.

- 4- tube fan coils in suspended celilings - Remote control - Fresh air renew: 25 m3/hour at each workstation and 30 m3/hour in meeting rooms.

- Air renewal peformed by mechanical ventilation (fresh air introduced/stale air removed in movement areas and adjacent areas).

- Aeraulic distribution performed by air handling units located in plant room, on terraces and in the basement.

- Office temperatures: Winter: indoor temperature + 22°C (plus or

minus 3°C). Summer: indoor temperature + 25°C (plus or

minus 1°C).

Smoke extraction - Common spaces and disabled people fireprotection area

- Atrium: mechanical.

Lifts - 2 sets of 3 lifts (800 kg) - 1.60 m/s. - 4 panoramic lifts (800 kg) - 1.60 m/s. - 4 goods lifts (820 kg) - 1.60 m/s. - 3 disabled lifts (2 x 250 kg and 1 x 336 kg). - 4 lifts for below-ground floors (630 kg) - 1.00 m/s.

- 1 goods lift for kitchens: 1,025 kg - 0.40 m/s.

Power supply - High - Cabling for workstations via raised floors with connection boxes for one high power strip per 10 m².

- Each power strip equipped with: 4 normal sockets, 2 x 16 A + earth, 3 UPS sockets, 2 x 16 A + earth,

Power supply - low - Operator room in basement. - Protective measures for cables and one 3 RJ 45 outlet per 10 m². > Occupier

- Electrical conduits available in common areas and leaseholders can install wiring rooms in private areas.

Back-up power supply (generator) - 400kVA generator, back-up power supply for safety systems (Safety Distribution Panel, Fire Safety System, emergency lighting).

Security - Security hub for access, monitoring and surveillance 24/7. - The whole building has a Class A fire safety system (type 1 alarm system, FDS and Fire Safety Centraliser).

- Badge readers for access to car parks and lifts. - Video surveillance at the different access points.

- Emergency exit door open sensors. - Broken glass sensors where premises directly give onto the outside and dual tech motion sensors in common areas (lift landings, halls, etc.).

- Protective measures for access monitoring equipment on every floor.

Building management system - Remote monitoring of all information relative to various of the systems installed: air-conditioning, heating, lighting and lifts.

Archives - Ventilated archive storage area in basement.

Acoustic feature - Offices: 35 dB (subject to exceptions).

Catering - On-site preparation capacity - 650 meals per day across 2.5 services between 11:45 AM and 2 PM.

- Restaurant seats approximately 260.

Car park - 2 storey underground car park with 157 parking spaces. - Dust-proof paint to floor. - Non-slip ramp.

Addresses 6-8, boulevard Haussmann - 75009 Paris 3-9, rue Chauchat - 75009 Paris 12-16, rue Le Peletier - 75009 Paris 13-15, rue Rossini - 75009 Paris

Regulations The building is governed by the French Labour Code

Floors - Haussmann: 8 floors, from 1st floor to 7th floor (8th floor mezzanine) + terrace.

- Rossini: 5 floors from Ground to 7th Floor - Car parks: Two storey underground

Technical features

6.8 HAUSSMANN - EN6.8 HAUSSMANN - EN6.8 HAUSSMANN - EN6.8 HAUSSMANN - EN6.8 HAUSSMANN - EN6.8 HAUSSMANN - EN6.8 HAUSSMANN - EN6.8 HAUSSMANN - EN6.8 HAUSSMANN - EN6.8 HAUSSMANN - EN6.8 HAUSSMANN - EN6.8 HAUSSMANN - EN6.8 HAUSSMANN - EN6.8 HAUSSMANN - EN6.8 HAUSSMANN - EN6.8 HAUSSMANN - EN6.8 HAUSSMANN - EN6.8 HAUSSMANN - EN6.8 HAUSSMANN - EN6.8 HAUSSMANN - EN6.8 HAUSSMANN - EN6.8 HAUSSMANN - EN6.8 HAUSSMANN - EN6.8 HAUSSMANN - EN6.8 HAUSSMANN - EN6.8 HAUSSMANN - EN6.8 HAUSSMANN - EN6.8 HAUSSMANN - EN6.8 HAUSSMANN - EN6.8 HAUSSMANN - EN6.8 HAUSSMANN - EN6.8 HAUSSMANN - EN6.8 HAUSSMANN - EN6.8 HAUSSMANN - EN6.8 HAUSSMANN - EN6.8 HAUSSMANN - EN